Magnetic flap level meter is common side mounted magnetic flap level meter and top mounted magnetic flap level meter two. So, what are the characteristics of the side-mounted magnetic level gauge, and what do you need to pay attention to in the process of its use?

magnetic level gauge

A, the characteristics of the side-mounted magnetic flap level meter

  1, simple structure, strong and reliable, no special maintenance.

  2, direct display of liquid level, not affected by the measured liquid high temperature, easy to flow, easy to burn, toxic and other characteristics.

  3、The flip-flop works without power supply, and can display the level change and alarm without disconnection.

  4、Can be used in vacuum, high pressure, high temperature environment, and can be applied to low density liquids.

  5、Strong corrosion resistance, suitable for most corrosive liquids.


magnetic level transmitter

Second, the use of side-mounted magnetic flap level meter key items

  1, side-mounted level meter and the measured container of the upper and lower liquid pipe between the best installed a cut-off valve to open or close the level meter; on the other hand, for the maintenance of the level meter to bring convenience. When the upper and lower shut-off valves are closed, the bottom drain flange of the level meter can be opened or the drain screw can be removed and the main body of the level meter can be cleaned by injecting water.

  2、When installing the level meter, the verticality of the centerline of the flange is ≤4‰. When the measuring range of the level meter is greater than 3 meters, it is necessary to consider increasing the middle reinforcement flange (or dopan) for fixed support to increase the strength.

  3, the supporting remote level transmitter and the secondary instrumentation between the isolation line, the core of the core area should be greater than 0.8mm. and AC power supply in the same way parallel laying, at least maintain a distance of more than 20 cm, it is best to wear a separate iron pipe laying, or with shielded two-core cable laying, shielding only one end grounding.

news-The characteristics of the side-mounted magnetic flap level meter and precautions for use-Kaidi

4, the choice of liquid level controller, its contact capacity are designed to resistive load, such as non-resistive or vigorous power load to use the intermediate relay conversion.

5, the liquid medium contains suspended impurities in the pro-magnetic material occasions, should not use this level meter, because these impurities will cause card resistance to the float assembly.

6, the blind area in the shape structure is related to the density of the medium. Therefore, different media have different blind areas.


  The above is the introduction of "side-mounted magnetic level indicator features and precautions for use", to learn more level switch (level switch, liquid level switch), level meter (level meter, liquid level meter) and other level measuring instrument knowledge, welcome to pay attention to and contact us! Email:info86kd@gmail.com