1. Product Principle
High Frequency Radar Level Meter 902T adopted 26G high frequency radar sensor, the maximum measurement range can reach up to 20 meters. Antenna is optimized further processing, the new fast microprocessors have higher speed and efficiency can be done signal analysis, the instrumentation can be used for reactor, solid silo and very complex measurement environment.
Principle
Radar level transmitter antenna microwave pulse is narrow, the downward transmission antenna. Microwave exposure to the medium surface is reflected back again by the antenna system receives, sends the signal to the electronic circuit automatically converted into level signals (because the microwave propagation speed, electromagnetic wave to reach the target and the reflected back to the receiver this time is almost instantaneous).
A Range set
B Min. adjustment
C Max. adjustment
D Blind area
Datum measurement: Screw thread bottom or the sealing surface of the flange.
Note: Make sure the radar level meter the highest level cannot enter the measuring blind area (Figure D shown below).
The characteristics of 26G radar level meter:
Ø Small antenna size, easy to install; Non-contact radar, no wear, no pollution.
Ø Shorter wavelength, and there is better reflection on the solid surface.
Ø The measurement blind zone is smaller, and good results can be obtained for the measurement of small tanks.
Ø Hardly affected by corrosion and slight foam.
Ø Hardly affected by water vapor, temperature and pressure changes.
Ø Severe dust environment will not affect electromagnetic wave work.
Ø High signal-to-noise ratio, better performance can be obtained even with fluctuations.
Ø The wave speed gathering effect is very good, with various types of antennas, it can meet 90% of the working conditions.
2. Product Introduction
902T
3. The Installation Requirements
Installation notes:
There should be no obstacles between the bottom of the antenna and the surface of the measured medium, and the installation in the tank should be avoided as much as possible, such as: human ladders, limit switches, heating equipment, brackets, etc. Also note that the microwave beam must not intersect the material flow.
When installing, pay attention to the maximum liquid level not to enter the blind area of the measurement; the instrument must be kept a certain distance from the tank wall; the installation of the instrument should make the antenna emission direction perpendicular to the surface of the measured medium as much as possible.
Instruments installed in explosion-proof areas must comply with the national installation regulations for explosion-proof hazardous areas. Explosion-proof instruments can be installed in places with explosion-proof requirements, and the instruments must be connected to the ground. The shell of the explosion-proof instrument is made of cast aluminum.
Installation location:
This product used to measure corrosive liquids, vapors, volatile liquids and to prevent condensation during measurement.
The instrument adopts flange connection and is installed at 1/4 or 1/6 of the diameter of the tank.
Note: The minimum distance from the tank wall should be 200mm.
Note: ① datum ②The container center or axis of symmetry
For the top of the flat conical tank, meter can be installed in the middle of the tank top to the bottom of the cone to ensure measurement.
Installation takeover height:
Antenna extends into the tank at least 20mm distance.
Typical installation errors:
Ø Conical tank
The instrument cannot be installed above the inlet.
Note: Sun-shading and rain-proof measures should be taken during outdoor installation..
①Correct ②Error rainproof measures
Ø The meter cannot be installed in the middle of the top of an arched or round tank. In addition to producing indirect echoes, it will also be affected by multiple echoes. Multiple echoes may be larger than the signal threshold of true echoes, because multiple echoes can be concentrated through the top, so they cannot be installed in the center.
①Correct ②Error
Ø When there are obstacles in the tank that affect the measurement, it is necessary to install a reflector to measure normally
①Correct ②Error
4. The Electrical Connection
The power supply voltage:
(4~20)mA/HART (Two wire system) | The power supply and the output current signal sharing a two core shield cable. The supply voltage range see technical data. For intrinsically safe type must be a safety barrier between the power supply and the instrument. |
(4~20)mA/HART(Four wire system) | Separate power supply and the current signal, respectively using a two-core shielded cable. The supply voltage range see technical data |
RS485 / Modbus(Four wire system) | Power supply and Modbus signal line separated respectively using a two-core shielded cable, the power supply voltage range see technical data. |
Cable Connection
General Introduction | Supply cable can use ordinary two-core cable, the cable diameter should be (6~12) mm, to ensure that the cable entry seal. If electromagnetic interference exists, recommended to use shielded cable. |
(4~20) mA/HART(Two-wire) | Supply cable can use ordinary two-core cable. |
(4~20) mA/HART(Four-wire) | Supply cable should be used with a dedicated ground cable. |
Modbus-RS485 | Shielded cable should be used for the power supply cable. |
Shielding and wiring | Both ends of the shielded cable should be grounded. Inside the sensor, the shield must be connected to the internal ground terminal. The external ground terminal on the enclosure must be connected to the ground. If there is ground current, the shielded cable must be grounded through a ceramic capacitor (for example: 1nF/1500V) far away from the shielding end of the instrument side to block direct and bypass high-frequency interference signals. |
Connection mode
Ø 24V 2-wire wiring diagram as follows:
Ø 6~24V Modbus-RS485 wiring diagram as follows:
Explosion Proof Connection
The explosion-proof form of this product is intrinsically safe.The intrinsic safety version sensors (Exia Ⅱc T6) use Alu-die casting housing and filling Silicone rubber sealants internal structure aimed to prevent sparks resulted from circuit failure from leaking out. It is applicable for the continuous level measurement of flammable medium under Exia Ⅱc T6.
A safety barrier FBS-2 must be used together with the intrinsic safety instrument. It is an associated device to this product for the power supply of this product. The main specification is intrinsic safety: ExiaⅡc, voltage of power supply: 24V DC±5%, short-circuit current: 135mA, operating current: 4...20mA.
All cables must be shielded. The max length is 500m for the cable from the barrier to the sensor. Stray capacitor≤0.1μF/Km, stray inductance 1mH/Km. Instrument must be connected to the ground potential. Any unapproved associated device is not allowed to be used.
Safety instructions:
Ø Please observe the local electrical code requirements!
Ø Please comply with local requirements for personnel health and safety regulations.
All electrical components of instrument operation must be completed by the formal training of professionals.
Ø Please check the instrument nameplate to provide product specifications meet your requirements. Please make sure that the power supply voltage and instrument nameplate on the requirements.
Protection grade:
This instrument meets the protection class IP66/67 requirements, please ensure the waterproof cable sealing head. The following diagram:
How to install to meet the requirements of IP67:
Please make sure that the sealing head is not damaged.
Please make sure that the cable is not damaged.
Please make sure that the cable for use with electrical connection specification.
Bend the cable down to ensure that water does not flow into the housing, see the①
Tighten the cable seal head, see the②
Please electrical interface will not use blind plug tight, see the③
5. Instrument Commissioning
Three kinds of debugging method:
1) Display / Button (With split display, you need to debug on the split)
2) Debug through computer software
3) HART Handheld programmer
Display / Button:
Debug the meter through the 4 buttons on the display screen. The debugging menu has four languages to choose from. The measured value can be read very clearly through the glass window.
Display / Button
① Liquid crystal display(LCD)
② Adjust by button
PC software debugging:
Connected to PC by HART
① USB interface ② Radar level meter ③ HART converter ④ 250 Ω Resistor
HART handheld programmer:
① HART handheld programmer ② Radar level meter ③ 250 Ω Resistor
6. Structure Size (Unit: mm)
The Outer Covering:
Cast aluminum shell
Plastic shell
Product size:
Flange type:
7. Technical Parameters
General data | |
Process connection | Thread G1½″A / Thread 1½″NPT / Flange |
Antenna Material | PVDF / PFA |
The outer shell material | Cast aluminum, plastic, stainless steel |
The seal between the shell and the shell cover | Silicone rubber |
Casing window | Polycarbonate |
The ground termina | Stainless steel |
The power supply voltage | |
Four wire system | 6~24V DC ( Modbus-RS485 ) / 198 ~242 VAC(Flameproof type /Double chamber) / 110 VAC(Flameproof type /Double chamber) |
Two wire system | DC 24V |
Power dissipatio | Max. 22.5mA / 1W |
Allowable ripple | - <100Hz Uss<lV - (100~100K) Hz Uss<l0mV |
The cable parameters | |
Cable entrance / plug | 1 M20xl.5 cable entrance 1 Blind plug (M20×l.5) |
Terminal | The maximum usable wire is 2.5mm² |
Output parameters | |
The output signal | (4 ~ 20) mA / Modbus-RS485 |
Resolution | 1.6μA |
Fault signal | Constant current output; 20. 5mA;22mA;3.9mA |
Two-wire load resistance | See below |
Four-wire load resistanc | Max 500Ω |
The integral time | (0 ~ 36) s, adjustable |
Blind area | the ends of the antenna |
The maximum distance measuremen | 20 meters |
Microwave frequency | 26GHz |
Communication interface | HART communication protocol Modbus-RS485 communication protoco |
The measurement interval | about 1 second (depending on the parameter settings) |
Adjust the time | about 1 second (depending on the parameter settings) |
Display resolution | 1 mm |
Working storage and transportation temperature | (-40~80) ℃ |
Process temperature (the temperature of the antenna part) | Standard type (40~130)℃ / High temperature type (40~230)℃ |
Relative humidit | ˂ 95% |
Pressure | Max. 1.0MPa |
Seismi | Vibration frequency (10~150) Hz, maximum vibration acceleration l0m/s² |
8. Meter Linearity
902T
The launch angle depends on the antenna size
-Φ63mm 14°
Accuracy See below(±5mm)
9. Product Model Selection
902F
License | |||||||||||||||||||||||||
P Standard (Non-explosion-proof) I Intrinsically safe (Exia ⅡC T6 Ga) G Flameproof (Exd ⅡC T6 Gb) | |||||||||||||||||||||||||
Process Connection / Material | |||||||||||||||||||||||||
Y Special Custom | |||||||||||||||||||||||||
Antenna Type / Material | |||||||||||||||||||||||||
A Horn antenna plus protective cover PVDF /200mm(standard) B Horn antenna plus protective cover PFA /200mm(standard) C Horn antenna plus protective cover PVDF /284mm(lengthen) D Horn antenna plus protective cover PFA /284mm(lengthen) | |||||||||||||||||||||||||
Seal Up / Process Temperature | |||||||||||||||||||||||||
V Viton / (-40~130) ℃ K Kalrez / (-40~230) ℃ | |||||||||||||||||||||||||
The Electronic Unit | |||||||||||||||||||||||||
3 (4~20) mA / 24V DC / HART 2-wire system 4 (4~20) mA / 220V AC / HART 4-wire system 5 Modbus-RS485 / 6~24V/ 4-wire system | |||||||||||||||||||||||||
Outer Covering / Protection Grade | |||||||||||||||||||||||||
L Aluminum / Single chamber / IP67 H Aluminum / Double chamber / IP67 G Plastic / Single chamber / IP65 K Stainless steel / Single chamber / IP67 | |||||||||||||||||||||||||
Cable Line | |||||||||||||||||||||||||
M M 20 ×1.5 N ½″ NPT | |||||||||||||||||||||||||
Field Display /The Programmer | |||||||||||||||||||||||||
A With X Without |