PP material magnetic flap level meter:
1. A side-mounted level gauge and a top and bottom pipette of the container under test * are equipped with a shut-off valve to open or close the level gauge, on the other hand, it is convenient to maintain the level gauge. When the upper and lower stop valves are closed, the drain flange at the bottom of the level gauge can be opened or the drain screw can be removed, and the body of the level gauge can be cleaned by pouring water.
2. When installing the liquid level gauge, the verticality of the flange center is ‰ 4 ‰. When the measuring range of the liquid level gauge is greater than 3 meters, you need to consider adding an intermediate reinforcement flange (or ear climbing) as a fixed support to increase the strength.
3. The connection between the supporting remote level gauge transmitter and the secondary meter requires the cross-sectional area of the core wire to be greater than 0.8mm2. When laying parallel to the AC power source, the distance should be at least 20 cm. * Laying through iron pipes alone, or using shielded two-core cables, the shield can only be grounded at one end.
4. The liquid level controller is selected, and its contact capacity is designed with a resistive load. If a non-resistive or high-power load is used, an intermediate relay is used to switch.
5. For liquids containing suspended impurities and magnetically-affinitive substances, this level gauge should not be used (because these impurities will cause blocking of the float assembly).