Unobstructed flow passage
No moving parts
No additional pressure drop
Favorable choice of materials for chemically aggressive liquids
Linear relationship between flow rate and measured variable
Low maintenance
Operates in both flow directions (forward and reverse)
Transit time meters unaffected by temperature, density and concentration
Later installation in existing pipe possible with individual elements, but onsite calibration required
Limitation:
Still problematic for liquid and gas measurements
Sound beam must traverse a representative cross section, therefore flow profile dependent. Long inlet and outlet sections required
Errors due to deposits
Transit time meters require clean liquids
Doppler meters only for slight contamination or few gas bubbles
Doppler meters affected by sound velocity changes due to temperature, density and concentration
Unsuitable for heavily contaminated liquids
Unobstructed flow passage without projecting parts
No moving parts
No additional pressure drop
Essentially flow profile insensitive, only short inlet and outlet sections required
Unaffected by changes in temperature, density, viscosity, concentration and electrical conductivity
Favorable choice of materials for chemically aggressive or abrasive measuring media
Unaffected by contamination and deposits
Especially suitable for hydraulic solids transport
Linear relationship between flow rate and measured variable
Operates in both flow directions (forward and reverse)
Measuring range setting can be optimized
Low maintenance, but still easy to maintain
Limitations:
For liquids only
Lower conductivity limit 0.05 μS/cm
Gas inclusions cause errors
No external power supply for Rotating vane and Woltman meters
Turbine type flow meter suitable for cryogenic liquids
Customized gas turbine flow meter usable at extreme temperatures and pressures
Disadvantages:
Limited choice of materials
Only for low viscosities
Moving parts, wear
Sensitive to contamination
Axial flow totalizers are flow profile sensitive
Inlet and outlet sections required (not for rotating vane meters)
Direct gas mass flow measurement
No pressure and temperature compensation required
Very low pressure drop
High measuring accuracy
Large span
No moving parts
Rugged construction
Short response time
Easily sterilized
Limitations:
For gases only
Inlet and outlet sections required